Use PT Series Part Number Crossover Tool to convert from 100, 200, 300 and 615 Series transmitters to new PT Series transmitters.
Use PT Series Part Number Crossover Tool to convert from 100, 200, 300 and 615 Series transmitters to new PT Series transmitters.
Items |
254-16-16/40inH2O-1-43-71-TC 25 Series 2" Tri Clamp, Range Adjustable from 0 - 16 inH2O to 0 - 40 inH2O, 0.2% of Adjusted Span, 4 to 20 mA/2-Wire + Hart® Protocol Sanitary Transmitter with PG9 Cable Gland and Transparent Cover |
254-16-29/145-1-43-71-TC 25 Series 2" Tri Clamp, Range Adjustable from 29 to 145 psig, 0.2% of Adjusted Span, 4 to 20 mA/2-Wire + Hart® Protocol Sanitary Transmitter with PG9 Cable Gland and Transparent Cover |
254-16-40/160inH2O-1-43-71-TC 25 Series 2" Tri Clamp, Range Adjustable from 0 - 40 inH2O to 0 - 160 inH2O, 0.2% of Adjusted Span, 4 to 20 mA/2-Wire + Hart® Protocol Sanitary Transmitter with PG9 Cable Gland and Transparent Cover |
|||
Description |
N/A
|
|||||
Type | N/A Pressure and Level Transmitter | |||||
Tri-Clamp Size | N/A 2 in | |||||
Weight | N/A 2.2 lb | |||||
Full Scale Best Fit Straight Line (BFSL) Accuracy (±) | N/A 0.2 % of adjusted span % | |||||
Storage Temperature [Min] | N/A -20 ºC-4 ºF | |||||
Storage Temperature [Max] | N/A 100 ºC212 ºF | |||||
Housing Material | N/A 304 Stainless Steel, 316 Stainless Steel | |||||
Output Signal | N/A 4 mA to 20 mA 2-wire, 4 mA to 20 mA 2-wire and Hart® signal | |||||
Electrical Connection | N/A PG9 cable gland | |||||
Environmental Rating | N/A Ingress Protection (IP66) (National Electrical Manufacturers Association (NEMA) 4X), Ingress Protection (IP68) (National Electrical Manufacturers Association (NEMA) 6) optional | |||||
Series | N/A 25 | |||||
Connection Material | N/A 316 Stainless Steel | |||||
Pressure Range | N/A 0 to 16 inH2O0 to 40 inH2O | N/A 29 to 145 psig0 to 803 inH2O0 to 4017 inH2O | N/A 1.45 to 5.8 psig0 to 40 inH2O0 to 160 inH2O | |||
Stability | N/A < 0.1%/year | |||||
Adjustment | N/A By 3 push buttons on display or optional Hart® signal | |||||
Response Time | N/A <100 ms | |||||
Service Life | N/A <10 yr | |||||
Measuring Element | N/A 316 Stainless Steel (Hastelloy C or Tantalum optional) | |||||
Limitations Which Apply Are |
N/A
These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation. In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice. |
|||||
Additional Information |
N/A
|
|||||
Options | N/A Transparent Cover (for Display) (TC) | |||||
Digital Indicators | N/A NOSHOK Digital Indicators provide local indication for pressure, level and temperature transmitters. | |||||
Sanitary Clamps and Gaskets |
N/A
1-1/2" (CR 12) 2" (CR 16) 2-1/2" (CR 20) 3" (CR 24) NBR Gasket 1-1/2" (BG 12) 2" (BG 16) 2-1/2" (BG 20) 3" (BG 24) PTFE Gasket 1-1/2" (TG 12) 2" (TG 16) 2-1/2" (TG 20) 3" (TG 24) |
|||||
Prop 65 Warnings |
N/A
WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
|||||
Stock | N/A | N/A | N/A Yes | |||
|