Print Back
  • Proven PT1000 platinum resistance sensor provides reliability, stability and unbeatable performance
  • Standard temperature ranges from -22 ºF to 302 ºF (-30 ºC to 150 ºC)
  • 4 mA to 20 mA transmitter included
Unit of Measure

Specifications

Type

N/A Transmitter

Connection Type

N/A Male National Pipe Thread (MNPT)

Seal Material

N/A 316 Stainless Steel

Low Calibrated Temperature Range

N/A -22 ºF

High Calibrated Temperature Range

N/A 302 ºF

Housing Material

N/A 316 Stainless Steel

Connection Size

N/A 1/4 in

Output Signal

N/A 4 to 20 mA, 2-Wire

Electrical Connection

N/A M12 x 1 (4-pin)

Power Supply

N/A 10 to 30 Vdc

Accuracy

N/A ±0.80 ºF (± 0.45 ºC)
Maximum uncertainty calculated @ maximum span, maximum measurement temperature, and ambient temperature. Maximum uncertainty includes Usensing element, Usensor measurement, Uoutput linearization.

Storage Temperature [Max]

N/A 85 ºC185 ºF

Storage Temperature [Min]

N/A -40 ºC-40 ºF

Series

N/A 810

Standard Temperature Ranges

N/A -22 to 302 ºF

Sensor Protection

N/A Burnout Protected from 3.3 to 23 mA

Measuring Element

N/A PT1000 Class A

Load Limitations

N/A ≤(Supply Voltage - 10 Volts)/0.023 A

Pressure Rating

N/A 3,915 psi

Ambient Temperature Range

N/A -40 to 185 ºF-40 to 85 ºC

Environmental Protection

N/A Ingress Protection (IP67)

Electrical Protection

N/A Reverse polarity, over-voltage and short circuit protection

Warranty

N/A 3 yr

Measuring Element Accuracy

N/A PT1000 Class A

Temperature Sensor Accuracy

N/A For ºF: ±[1.8*(0.15 + 0.002 (t - 32) / 1.8)]
For ºC: ±(0.15 K + 0.002 I t I) per EN 60751

Sensor Diameter

N/A 6 mm

Sensor Length

N/A 1 in

Industry Standards/Certifications

N/A European Conformity (CE) Compliant to Electromagnetic Compatibility (EMC) per EN 61326
Radio Frequency Interference (RFI), Electromagnetic Interference (EMI) and Electrostatic Discharge (ESD) Protection

Prop 65 Warnings

Prop 65 Warnings

N/A
WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Limitations Which Apply Are

Limitations Which Apply Are

N/A These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation.

In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice.

Thermowells

Thermowells

N/A Thermowells allow a temperature instrument to be removed and replaced without shutting down and draining the process, and reduce the possibility of damage to the temperature instrument.

Application

Application

N/A
  • Mobile hydraulics
  • Automotive
  • Heat exchangers
  • HVAC
  • Transportation
  • Refrigeration controls