About
- Accepts a variety of standard process signals and precisely scales them into any desired unit of measurement
- Single input or dual input
- Employs advanced technology for stable, drift-free readout
- Field upgradeable with plug-in option cards; including 4 set point alarms, analog output and serial communication
- 16 point scaling for non-linear processes
- Max. and min. value display
Featured Specifications
Series
Dual Input
Non-Condensing Humidity
85 %
Option Cards
No Option Card
Documents
Product Specifications|Additional Information|Options and Accessories|Applications|Limitations Which Apply Are
Product Specifications
▲| Type | Digital Indicator |
| Series | Dual Input |
| Process Display | 5 digit, 0.56" Red LED |
| Accuracy | <0.03% of full scale, 64 ºF to 82 ºF (18 ºC to 50 ºC) <0.12% of full scale, 32 ºF to 122 ºF (0 ºC to 50 ºC) |
| Storage Temperature ºF | -40 to 140 ºF |
| Storage Temperature ºC | -40 to 60 ºC |
| Effect | ≤0.1 % |
| Full Scale Temperature ºF | 18 ºF |
| Full Scale Temperature ºC | 10 ºC |
| Environmental Rating | National Electrical Manufacturers Association (NEMA) 4, National Electrical Manufacturers Association (NEMA) 4X, Ingress Protection (IP65) (Front of Display Only) |
| Input Signals Current | 4 to 20 mA |
| Direct Current (DC) Transmitter Power Supply Voltage | 24 V |
| Key Pad | 3 programmable function keys, 5 total |
| Power Requirement | AC version 85 Vac to 250 Vac, 50/60 Hz, 15 VA, DC version 11 Vdc to 36 Vdc, 11 W |
| Electrical Connection | Screw terminals at back of case |
| Memory | Electrically Erasable Programmable Read-Only Memory (EEPROM) |
| Non-Condensing Humidity | 85 % |
| Vibration Hz | 5 to 150 Hz |
| Shock | 25 g |
| Normal Rejection Mode | 60 dB |
| Normal Rejection Mode Frequency |
|
| Altitude | Up to 2,000 m |
| Update Rate | 200 ms |
| Selectable Filtering | 0 to 25 s |
| Linearization | 2 to 16 points, selectable |
| Reading [Min/Max] | Captures and stores min/max measurement |
| User Inputs | 3 programmable, 30 Vdc max. continuous |
| Sensor Excitation | Built-in 24 Vdc |
| Totalizer Time Base | Second, Minute, Hour or Day |
| Totalizer Time Batch | Can accumulate from user input |
| Electromagnetic Rating | European Conformity (CE) Compliant to Electromagnetic Compatibility (EMC) Norm European Standards (EN) 61326-1, Radio Frequency Interference (RFI), Electromagnetic Interference (EMI) and Electrostatic Discharge (ESD) Protection |
| Weight | 10.4 oz |
| Warranty | 2 yr |
| Options | Resistance Temperature Device (RTD), Thermocouple |
| Option Cards | No Option Card |
Additional Information
▲| Additional Information |
|
Options and Accessories
▲| 2000/2100 Series Smart System Intelligent Digital Indicator Option Cards |
|
| AC to DC Retrofit Package |
|
| NEMA 4 Enclosure - 1950 Series Digital Indicator |
|
Applications
▲| Application |
|
Limitations Which Apply Are
▲| Limitations Which Apply Are | These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation. In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice. |