About

Intelligent Line Powered Panel Meter Analog, 12-24 VDC/VAC, SunBright, 0.6 in, Dual Line, 6 Digits, Red LED, 2 Relays

Featured Specifications

Power

12-24 Vdc or 12-24 Vac ±10%, 15 W max

Display Brightness

SunBright, 0.6 in, Dual Line, 6 Digits, Red LED

Option Cards

2 Relays

Product Specifications

▲
Note
Except where noted, all specifications apply to operation at +25°C
Memory
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost
Weight
9.5 oz (269 g)
Display
Dual-Line 6-Digit Display, 0.6" (15 mm) & 0.46" (12 mm)
Accuracy
±0.03% of calibrated span ±1 count; square root & programmable exponent accuracy range: 10-100% of calibrated span
Altitude
Up to 2,000 meters
Humidity
0 to 90% non-condensing
Filtering
0 to 25 seconds, selectable
Indications
4 front-panel alarm status LEDs (1 per relay/set point), independent of relay status; available even on meters without relays installed
Keypad Type
4 front panel buttons
Update Rate
5/second (200 ms)
User Inputs
F4 digital input — remote operation of front-panel buttons, relay acknowledge/reset, max/min reset
Warranty
3 yr
Option Cards
2 Relays
Input Signals
Field selectable: 0-20 mA, 4-20 mA, ±10 V (0-5 V, 1-5 V, 0-10 V)
Linearization
2 to 32 points (PV1); 2 to 8 points (PV2, dual-scale)
Input Overload
Current input protected by internal resettable fuse, 30 VDC max; auto-resets after fault clears
Product Series
IDE30
Min/Max Reading
Captures and stores min/max measurement
Power Requirement
12-24 Vdc or 12-24 Vac ±10%, 15 W max
Sensor Excitation
Isolated 24 Vdc @ 200 mA Transmitter Power Supply
Temperature Drift
Input: 0.005%/°C max (0 to 65°C ambient), 0.01%/°C max (-40 to 0°C ambient)
Display Brightness
SunBright, 0.6 in, Dual Line, 6 Digits, Red LED
Environmental Rating
UL Type 4X, NEMA 4X, IP65 (front panel only); panel gasket provided
Electrical Connection
Screw terminals at back of case; accepts 12 to 22 AWG wire
Normal Mode Rejection
Greater than 60 dB at 50/60 Hz
Electromagnetic Rating
EN 55022 Class A emissions; EN 61326-1 & EN 61000-6-2 immunity; CE compliant
Power Resistance [Max]
Output loop resistance: 10-700 Ω (24 VDC internal supply); 100-1200 Ω (35 VDC external supply)
Power Consumption [Max]
AC version: 20 W max; DC version: 15 W max
Storage Temperature Range
-40 °F to 185 °F (-40 °C to 85 °C)
Operating Temperature Range
-40 °F to 149 °F (-40 °C to 65 °C)

Applications

▲
Application
  • Process indication
  • On/off pump controls
  • Compressor controls
  • Safety or shutdown alarms
  • Local indication with signal
  • Retransmission to computer control system

Prop 65 Warnings

▲
Prop 65 Warnings
⚠️ WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov