About
Multivariable Controller with CE, cULus general electrical safety, 90 - 264 Vac, 4 Analog Inputs, 4 Temperature Inputs, TCP/IP Ethernet Connectivity
Featured Specifications
Power
90-264 Vac, 47 to 63 Hz, 60 W max
Expansion Cards
4 Analog Inputs, 4 Temperature Inputs
Communications
TCP/IP Network
Assets
Product Specifications
▲| Weight | Total weight dependent on specific configuration |
| Accuracy | Analog Inputs: ±0.03% of full scale ±1 count; Temperature Inputs: Varies by selected sensor type |
| Altitude | Up to 2,000 m (6,562 ft) |
| Humidity | 0 to 90% non-condensing |
| HMI Display | Color QVGA (320 x 240 pixels), 5.7" (145 mm) diagonally, white backlight; bargraph (20 divisions); numeric up to 15 digits |
| PID Control | Auto-Tune PID Control for multiple control loops with Analog, Digital, or Relay Outputs |
| Warranty | 3 yr |
| Data Logging | Optional Add-On (PDK9000D1): USB data logger, up to 8 logs, 12 variables/log |
| Communications | TCP/IP Network |
| Product Series | IDE40 |
| Expansion Cards | 4 Analog Inputs, 4 Temperature Inputs |
| Number of Alarms | Up to 64 high/low alarms with AND/OR logic combination |
| Power Requirement | 90-264 Vac, 47 to 63 Hz, 60 W max |
| Temperature Drift | Analog Inputs: better than 20 ppm/°C (-40 to 60°C ambient); Temperature Inputs: ±2°C max (0 to 55°C ambient), ±4°C max (-25 to 0°C ambient) |
| Display Update Rate | User selectable: 0.1 to 0.5 sec (10 to 2 updates/sec) |
| Environmental Rating | UL Type 4X, NEMA 4X, IP66; panel gasket provided |
| Electrical Connection | Removable screw terminal blocks; Analog/Relay I/O: 12-24 AWG; Digital I/O: 16-30 AWG; RS-485: 12-24 AWG; RJ45 Ethernet; Micro-USB (programming) |
| Storage Temperature Range | -40 °F to 140 °F (-40 °C to 60 °C) |
| Hazardous Location Ratings | UL & C-UL Listed for Ordinary Locations (US/Canada): UL 508 Industrial Control Equipment, UL File E160849; CSA-C22.2 No. 61010-1 & 61010-2-201, UL 61010-1 & 61010-2-201 ⚠ CONFLICTS WITH DATASHEET ORDERING RULE — datasheet states models with the Temperature Inputs Card are not UL & C-UL Listed and should only be ordered as N (no approvals); verify with factory before finalizing this record. |
| Operating Temperature Range | -13 °F to 131 °F (-25 °C to 55 °C) |
Applications
▲| Application |
|
Prop 65 Warnings
▲| Prop 65 Warnings | ⚠️ WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |