About
Intelligent Pressure Transmitter IO Link, 0 to 16 bar gauge, ±0.50% of span, non-linearity best fit straight line per IEC 61298-2 at reference conditions, one switching output (PNP), IO-Link 1.1, 1/4 NPT male, M12 x 1 4 pin with integral indication
Featured Specifications
Accuracy
0.50% full scale
Output Signal
IO-Link v 1.1 (1 configurable output, PNP)
Process Connection
1/4" NPT Male
Electrical Connection
M12 x 1 (4-pin)
Assets
Product Specifications
▲| Pressure Range | 0 barg to 16 barg (0 psig to 232 psig) |
| Service Life | 100,000,000 cycles (MTTF > 100 years) |
| Ambient Temperature Range | -22 to 212 ºF
-30 to 100 ºC |
| Compensated Temperature Range | -4 to 176 ºF
-20 to 80 ºC |
| Media Temperature Range | -22 to 212 ºF
-30 to 100 ºC |
| Humidity | 45 - 75% r.h. |
| LED Status | Green: Operation, Yellow: Warning, Red: Error |
| Current Consumption | ≤25 mA, ≤0.3 A including switching current (one switching output) |
| Proof Pressure | 2 Times |
| Measuring Element | 316L, PH grade Stainless Steel |
| Housing Material | 316L Stainless Steel |
| Connection | PBT GF30, 316L Stainless Steel |
| Environmental Rating | IP65 and IP67 per IEC 60529 |
| Electromagnetic Rating | RFI, EMI and ESD protection |
| Electrical Protection | Reverse polarity, over-voltage and short circuit protected |
| Shock | 100 g, 6 ms, mechanical |
| Vibration | 25 g, 10 to 2,000 Hz |
| Weight | 2.8 oz |
Output Parameters
▲| Output Number | 1 output, adjustable via IO-Link (PNP) |
| Output Function | Normally open, normally closed, window and hysteresis (adjustable via IO-Link) |
| Switching Current | Max 250 mA |
| Response Time | <5 ms |
| Zero Point Offset | Max 3% of span (via IO-Link) |
| Damping | 0 ms to 65 ms (via IO-Link) |
| Switch On Time | 1 s |
| Switching Voltage | Power Supply - 1 V |
| Accuracy | 0.50% full scale |
| Long Term Drift | ≤0.10% of span (per 1 year) |
| Temperature Error | ≤1.5% of span |
| Temperature Coefficients | Mean TC zero point/Mean TC span: ≤ 0.10% of span/10K from -22 °F to 212 °F (-30 °C to 100 °C) |
Applications
▲| Application |
|
Limitations Which Apply Are
▲| Limitations Which Apply Are | These units must be operated within the cataloged environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation. In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice. |
Prop 65 Warnings
▲| Prop 65 Warnings | ⚠️ WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |