Intelligent Indicating Transmitter/Switch, 0 psig to 200 psig, ±0.5% Accuracy (BFSL), 1 N.O. or N.C. switch (PNP/NPN) with 4 mA to 20 mA/0 Vdc to 10 Vdc, 4 mA to 20 mA or 0 Vdc to 10 Vdc Output, 1/4" NPT male, M12 x 1 (4-pin), With IO-Link

Featured Specifications

Accuracy

±0.5% of span (BFSL)

Switch Adjustable Range

.25 to 100% of full scale

Process Connection

1/4" NPT Male

Electrical Connection

M12 x 1 (4-pin)

Product Specifications

▲
Pressure Range
0 psig to 200 psig
Display
14 segment-LED, red 4-digit, height 0.35"
Service Life
100,000,000 load cycles
Ambient Temperature Range
-4 to 176 ºF -20 to 80 ºC
Compensated Temperature Range
32 to 176 ºF 0 to 80 ºC
Media Temperature Range
-4 to 185 ºF -20 to 85 ºC
Current Consumption
Max. 70 mA (with 4-20 mA output signal); Total max. 600 mA including switching current
Proof Pressure
2 times full scale
Measuring Element
316L, PH grade Stainless Steel
Housing Material
304 Stainless Steel
Connection
316 Stainless Steel
Materials of Construction (Wetted Parts)
316L, PH grade Stainless Steel
Environmental Rating
IP65 and IP67 per IEC 60529
Electromagnetic Rating
RFI, EMI and ESD protection
Electrical Protection
Protected against reverse polarity, over-voltage and short circuit
Shock
50 g
Vibration
20 g
Weight
0.49 lb

Output Parameters

▲
Output Number
1
Output Function
N.O. or N.C.
Switching Current
250 mA max.
Switching Voltage
Power Supply - 1 V
Switch On Time
1 s
Response Time
<5 ms
Adjustment
Freely scalable within the range of 5:1

Switch Parameters

▲
Switch Adjustable Range
.25 to 100% of full scale
Switch Point
.25 to 100% of full scale
Switch Type
PNP or NPN Electronic Switch
Switching Function
N.O., N.C., window, hysteresis (freely adjustable)
Switching Number
1
Hysteresis
Fully adjustable
Non-Repeatability
<0.1% of span (IEC 61298-2)
Contact Rating
250 mA max.

Accuracy Parameters

▲
Accuracy
±0.5% of span (BFSL)
Note for Accuracy
Transmitter accuracy: includes non-linearity, hysteresis, zero offset and end value deviation (corresponds to measured error per IEC 61298-2). Switch accuracy: ≤0.5% of span. Non-repeatability: <0.1% of span (IEC 61298-2).

Applications

▲
Application
  • Hydraulics & pneumatics
  • Power generation
  • Pumps & compressors
  • Stamping & forming presses
  • Water & wastewater

Limitations Which Apply Are

▲
Limitations Which Apply Are
These units must be operated within the catalogued environmental and application parameters. Determination of failure will be made by NOSHOK, Inc.'s equipment and personnel or a certified test facility specializing in this type of evaluation. Gauge failures determined to be caused by over-range, incompatibility with environment or product media and abuse will not be considered under this warranty. NOSHOK, Inc. will, at its discretion, repair or replace the working parts of the damaged gauge without cost to the customer.

In keeping with and for purposes of product and/or manufacturing process improvements, NOSHOK, Inc. reserves the right to make design changes without prior notice.

Prop 65 Warnings

▲
Prop 65 Warnings
⚠️ WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov