About
868 Series 0 to 5 psid Pressure Range and 1/4" National Pipe Thread (NPT) Fittings Differential Pressure Sensor Control Level Transmitter
Featured Specifications
Pressure Range (psid)
0 to 5 psid
Output Signal
4 to 20
Product Specifications|Pressure Ranges|Options and Accessories|Temperature Ranges|Features|Applications|Additional Information|Warnings|Note
Product Specifications
▲| Series | 868-D/P Sensor Control (Air Flow Control) |
| Type | Sensor Control Level Transmitter |
| Range of Adjustment | 0 to 83 inH2O through 0 to 138 inH2O, 0 to 2.1 mH2O 0 to 3.5 mH2O |
| Combined Accuracy | ± 0.34% Full Scale |
| Fittings | None, 1/4 in. National Pipe Thread (NPT) |
| Accuracy | ± 0.2% Full Scale (± 0.10% Full Scale, Typical) Includes Non-Linearity, Hysteresis and Non-Repeatability |
| Thermal Effects (Over Compensated Temperature Range) | Less than 0.007% ºF (0.011% ºC) Span Shift - Sensitivity Less than 0.007% ºF (0.011% ºC) Span Shift - Zero |
| Depth Measurement [Max] | 1,937 inH2O |
| Power Supply Stability (Effect on Free-Space Optical Communication (FSO)) | Less than 0.005% of Span Change in Output Per Volt Change at Input Terminals |
| Output Signal | 4 to 20 |
| Direct Current (DC) Power Supply Voltage (Unregulated) | 14 to 40 V |
| Repeatability | ± 0.20% of Calibrated Span |
Pressure Ranges
▲| Nominal Span Adjustment Range | 0 to 5 psid |
| Burst Pressure | 200 psi |
| Pressure Range (psid) | 0 to 5 psid |
| Compressed Air Requirement | 35 psid to 150 psig Supply Pressure at Control Inlet |
| Operating Limit (Maximum Pressure) | Pressure above 300% nominal range (overrange) will result in damage to the transmitter (200% may cause a shift in calibration). Burst pressure is 200 psi and will cause catastrophic and physical failure of the pressure element. |
Options and Accessories
▲| Service and Replacement Parts | 7333-10: Replacement filter element 7334-2: SafeGard service kit 7334-9: Air control section kit 7879-20: Vent generator 9316-4: O-ring for D/P top plate (868) |
Temperature Ranges
▲| Compensated Temperature Range | 32 to 120 ºF
0 to 54 ºC |
Features
▲| Differential Pressure Pneumatic Sensor Controls | The KING-GAGE® D/P Transmitter is also offered in a hybrid version combined with an air flow control for pneumatic sensors or downpipe (bubbler) systems. These combination units allow for direct 4-20 mA signal from the tank using the integrated differential pressure transmitter. D/P Sensor Controls are designed for use with KING-GAGE® pneumatic diaphragm sensors. The air control portion of these units creates a 1:1 pneumatic pressure directly proportional to liquid depth in the tank. Acting as a force balance, the pneumatic pressure offsets the hydrostatic pressure exerted against a diaphragm at the tank. The electronic transmitter then converts this pressure into a 4-20 mA output signal. D/P LiquiSeal Controls and D/P Purge Controls are used in conjunction with a downpipe (or bubble tube) extending down through the liquid contents of the tank. This type of sensor also acts as a force balance. A continuous purge of compressed air into the pipe displaces the liquid and creates a pneumatic pressure equivalent to hydrostatic head pressure. The transmitter converts this pressure into a 4-20 mA output signal. |
Applications
▲| Applications |
|
Additional Information
▲| Additional Information |
|
Warnings
▲| Product Warranty | All KING-GAGE®, a NOSHOK Company products are guaranteed to be free from defects in material and workmanship for one (1) year from the date of purchase. Repair Services Warranty: 90 days limited warranty. |
| Prop 65 Warnings | ⚠️ WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Note
▲| Note | Unit includes (1) water-resistant Hubbell cord grip. |