About
5600 Series 0 to 5 psid Pressure Range and Swagelok 1/4" Tube 1/4" Tube x 1/4 National Pipe Thread (NPT) (Compatible with Copper or Poly Tubing) Fittings Differential Pressure Level Transmitter
Featured Specifications
Pressure Range (bar)
0 to 0.3 bar
Pressure Range (psid)
0 to 5 psid
Accuracy
± 0.34% Full Scale
Output Signal
4 to 20
Product Specifications|Pressure Ranges|Temperature Ranges|Applications|Additional Information|Warnings
Product Specifications
▲| Series | 5600 |
| Type | Differential Pressure Level Transmitter |
| Range of Adjustment | 0 to 83 inH2O through 0 to 138 inH2O, 0 to 2.1 mH2O 0 to 3.5 mH2O |
| Material | Machined brass body with acrylic semi-gloss enamel finish; integral filter element is aluminum with acrylic semi-gloss enamel finish |
| Accuracy | ± 0.34% Full Scale |
| Fittings | Swagelok 1/4 in. Tube 1/4 in. Tube x 1/4 National Pipe Thread (NPT) (Compatible with Copper or Poly Tubing) |
| Depth Measurement [Max] | 1,937 inH2O |
| Output Signal | 4 to 20 |
| Direct Current (DC) Power Supply Voltage (Unregulated) | 14 to 40 V |
| Repeatability | ± 0.20% of Calibrated Span |
| Flow Rate (Air Purge) | Nominal 1 cfh (Cubic Feet Per Hour) at Specified Differential Maximum Air Consumption Under 5 cfh (Cubic Feet Per Hour). |
| SafeGard Option | An adjustable pressure-limiting control that permits pre-setting a maximum value for pressure output from the Purge Control. SafeGard range available as 25 inH2O to 650 inH2O or 650 inH2O to 1750 inH2O |
Pressure Ranges
▲| Nominal Span Adjustment Range | 0 to 5 psid |
| Pressure [Max] | 300% Over-Range |
| Burst Pressure | 200 psig |
| Pressure Range (Bar) | 0 to 0.3 bar |
| Compressed Air Requirement | 35 to 150 psig Supply Pressure at Control Inlet |
| Operating Limit (Maximum Pressure) | Pressure above 300% nominal range (overrange) will result in damage to the transmitter (200% may cause a shift in calibration). Burst pressure is 200 psi and will cause catastrophic and physical failure of the pressure element. |
| Differential Pressure Purge Control | Unit incorporates differential air flow regulator with flow control orifice Fixed differential set to nominal 10 psid Output is 1:1 pneumatic pressure (hydrostatic force equivalent) Includes an integral differential pressure (D/P) transmitter converting pneumatic pressure into 4 mAdc to 20 mAdc electronic output |
| Differential Pressure Pneumatic Sensor Controls | The KING-GAGE® D/P Transmitter is also offered in a hybrid version combined with an air flow control for pneumatic sensors or downpipe (bubbler) systems. These combination units allow for direct 4-20 mA signal from the tank using the integrated differential pressure transmitter D/P Sensor Controls are designed for use with KING-GAGE® pneumatic diaphragm sensors. The air control portion of these units creates a 1:1 pneumatic pressure directly proportional to liquid depth in the tank. Acting as a force balance, the pneumatic pressure offsets the hydrostatic pressure exerted against a diaphragm at the tank. The electronic transmitter then converts this pressure into a 4-20 mA output signal. D/P LiquiSeal™ Controls and D/P Purge Controls are used in conjunction with a downpipe (or bubble tube) extending down through the liquid contents of the tank. This type of sensor also acts as a force balance. A continuous purge of compressed air into the pipe displaces the liquid and creates a pneumatic pressure equivalent to hydrostatic head pressure. The transmitter converts this pressure into a 4-20 mA output signal. |
Temperature Ranges
▲| Compensated Temperature Range | 32 to 120 ºF
0 to 54 ºC |
Applications
▲| Applications |
|
Additional Information
▲| Additional Information |
|
Warnings
▲| Product Warranty | All KING-GAGE®, a NOSHOK Company products are guaranteed to be free from defects in material and workmanship for one (1) year from the date of purchase. Repair Services Warranty: 90 days limited warranty. |
| Prop 65 Warnings | ⚠️ WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Applications
▲| Application |
|